- Depressurize and isolate the transmitter. If opening the transmitter exposes voltages beyond the Instrinsic Safe (I.S.) rating use a continuous monitoring gas detector to monitor for explosive gases.
- Plumb the transmitter to the 1/8 inch NPT pressure port of the 718Ex. Connect the test leads per the figure above.
- Turn the calibrator on. Vent the calibrator and press zero to zero the pressure displayed. Close the vent control.
- Press the UNITS key until PSI shows in the display.
- With the 718Ex’s bleed valve open to atmosphere, press the ZERO key. Close the bleed valve. Set the pressure / vacuum valve to +, for positive pressure.
- Use the hand pump to apply roughly 3 psi to the transmitter. Partial pump strokes will apply small increments of pressure. Use the fine-adjust knob to get reasonably close to 3.00 psi.
- Press the HOLD key, and record the psi and mA readings. Press the HOLD key to resume reading.
- Calculate and record the error, using: Error = ([(i-4)/16] – [(P-3)/12]) * 100 where Error is in % of span, i is your measured current in mA and P is your measured pressure in psi.
- Repeat steps 5 through 7 at mid-range, around 9 psi, to check linearity at mid-span.
- Repeat steps 5 through 7, now at 15 psi, for a check at 100 % of span.